|
Frequently Asked Questions
Design Safety Standards and Electrical Systems
(The
following are Technical Interpretations provided
by the Florida Department of Labor and Employment
Security)
| Q: |
Do circuit breakers in panel boxes
have to be labeled? If so, do labels need
to be next to breakers or can they be on
the outer door of the panel box? |
| A: |
Yes,
labeling is required. Each circuit breaker
or disconnect switch must be clearly marked
to indicate its purpose. Labels cannot
be on the outer door of the panel box unless
there is only one circuit breaker in the
panel box. A labeling system must be located
on the inside of the panel box door or
next to each circuit breaker. {29
CFR 1910, Subpart S, Electrical; Subsection
303 (f)} |
| |
|
| Q: |
How would the ground to path requirement
covered under 1910.304 (f) (4) apply to
buildings having a 2-wire system? |
| A: |
Older
wiring systems with outlets designed for
2-prong receptacles may be found in buildings
built before March 1972. These receptacles
accept 2-prong plugs without a grounding
pin. Current wiring codes, however, require
outlets to be designed for 3-prong receptacles.
The path to ground requirement for electrical
systems with either 2 or 3-prong receptacles
must be permanent and continuous. If the
outlet is designed to be part of the permanent
wiring of the building, then the wiring
is permanent. Converting a 2-prong receptacle
to accept a 3-prong plug by using a plug-in
adapter with or without a grounding wire
is not acceptable because it is not part
of the permanent wiring of the building. {29
CFR 1910.302 and 1910.304; NFPA 70E} |
|